Digital Tachometers, RPM , Speed Indicators,counters, timers,Amp-Hour/Amp-Minute Meters,Humidity Indicators/Controllers,Conductivity Indicators,pH/ORP Indicators/Controllers,Temperature Indicators,Process Controllers,Calibrators,Transmitters/Converters ,Flow Indicators and Controllers

Home New Products Contact Us
About Us Products Feedback Contact Us

 
Model 6652

 

 


Universal Temperature Controller with 2 Set Points


Features

  • Microprocessor based controller, linearised for PT100 sensor & 3 thermocouples (J,K,R) with Auto cold junction compensation
  • Separate displays for Temperature and Set Point
  • Separate heater & cooler/alarm logic relays
  • Offset digitally programmable from front
  • Configuration lockable by rear jumper
  • Proportional/On-Off control user selectable
  • User programmable hysterisis band
  • Percentage on time settable to avoid overshoots and save power
  • Non-volatile memory to save settings
  • Aesthetically designed front panel with membrane switches
Specification

Display :4 digit 0.56± 7 segment Red LED display for Temperature  height Red
:4 digit 0.56± 7 segment Green LED display for Set Point
Range :J T/C:0 to 750°C K T/C:0 to 1250°C R T/C:0 to 1700°C PT100: -100.0 to 600.0°C
Sensor :J,K,R & 3 wire PT100
Accuracy : ±0.1% of Full Scale ±1 digit
Relay Logic :On/Off or time proportional with 20 sec cycle time for heater relay (Relay 1) On/Off for Cooler / Alarm Relay (Relay 2). 5 Amps/220V AC Relay Contact outputs
Profiles :Up to 4 separate profiles, each with 9 segments programmable as Ramp or Soak with individual Slopes, Time Intervals and Set Points
Ramp Rate/Segment :Settable from 0-999°C/Hr
Soaking Temp/Segment :0 - 1250°C
Soaking Time/Segment :0 ±99.99 Hrs
Power Supply :220V AC ± 15% at 50Hz
Proportional Band : -7.0 °C to +3.0 °C around set point with 10% per degree cut
Hysterisis Band : Settable from 0°C to 20.0°C
Percentage Power : User programmable from 0% to 100% to avoid overshoots and save power
Memory : Non-volatile EEPROM to save settings
Configuration Lock : On rear terminals to prevent tampering with configuration except Set Point
Supply : 220V AC 15% @ 50/60Hz
Dimensions : Front Fascia: 96mm x 96mm x 135mm.
Cut Out : 91mm x 91mm
Offset :Settable from -20.0°C to +20.0°C