A temperature controller reads a sensor, compares the reading with the set point you enter, and switches or modulates a heater, cooler or valve to close the gap. Everything else on the specification sheet — input types, control algorithm, outputs, alarms — decides how well it does that job for your particular process.
| Sensor | Typical range | Best for |
|---|---|---|
| J thermocouple | 0 to about 750 °C | Plastic machinery, ovens, general heating |
| K thermocouple | 0 to about 1250 °C | Furnaces, kilns, heat treatment |
| R thermocouple | up to about 1700 °C | Very high temperature furnaces, glass |
| PT100 (3-wire RTD) | -100 to +600 °C | Pharma, food, cold rooms, autoclaves, anywhere accuracy matters |
| 4–20 mA | Scaled to any range | When a transmitter is already installed |
The controller must be set for the same sensor type you connect. A K thermocouple read on a J setting can be off by tens of degrees. Thermocouple inputs also need cold junction compensation and the correct compensating cable — ordinary copper wire introduces errors. For the trade-offs, see PT100 vs thermocouple.
The output is fully on below the set point and fully off above it, with a small hysteresis band to stop chattering. It is simple and robust, but temperature always oscillates around the set point. That is fine for water tanks, cold rooms and simple ovens.
PID (proportional–integral–derivative) varies the heater power continuously, so the temperature settles at the set point with little overshoot. Use it for extruders, moulding machines, lab ovens, baths and any process where a few degrees matter. Most modern PID controllers have auto-tune, which finds the P, I and D values for you.
| On/off | PID | |
|---|---|---|
| Stability | Swings a few degrees | Typically within ±1 °C |
| Setup | Set point + hysteresis | Auto-tune, then fine-tune |
| Contactor wear | Low (slow switching) | High if relay cycles fast — use SSR |
| Typical use | Tanks, cold rooms, simple heaters | Extruders, ovens, baths, furnaces |
Common DIN cut-outs are 48 × 48, 48 × 96, 72 × 72 and 96 × 96 mm. Choose the size that fits your existing panel cut-out to avoid metal work. Check the supply: most Indian panels run on 230 V AC, while export machines may need 110 V AC / 60 Hz or 24 V DC — Countronics builds all of these on request.
PID gives tighter, steadier temperature with little overshoot and suits extruders, ovens and baths. On/off is simpler and fine for tanks, cold rooms and processes where a swing of a few degrees is acceptable.
Yes. Universal controllers let you select J, K, R thermocouple or PT100 from the menu. The selected type must match the sensor actually connected.
Use an SSR output for PID when the cycle time is short. A mechanical relay switching every few seconds wears out quickly; relays suit on/off control or long PID cycle times.
Auto-tune briefly drives the process up and down, measures how it responds and calculates suitable P, I and D values, so you do not need to tune by trial and error.
Yes. Standard units run on 230 V AC, and 110 V AC / 60 Hz, 12 V DC and 24 V DC versions are available on request.
Countronics makes on/off and PID temperature controllers for thermocouple and PT100 sensors. Tell us your process, sensor and panel size and we will suggest the right model.