Category: Conductivity Meter Indicator Controller
SKU: 160-COND
Features
- Auto/Manual temperature compensation selectable
- Conductivity and TDS selectable from front panel
- Cell Factor selectable for both 1.0 and 0.1
- 4 Step Range selection 0.1µs to 199.9ms for conductivity
- Digital calibration for Conductivity/TDS
- Auto Temp Compensation using PT100 sensor
- Dual set limit with separate relay outputs
- Settable hysteresis for both set limits
- Bright Red LED display with separate display for set limit-1
- Aesthetically designed front panel with membrane switches and ABS cabinet
Specification
Display | 0.56” Red LED 7 segment Display for Conductivity/TDS 0.56” Red LED 7 segment Display for Set-Limit-1 |
Resolution | Conductivity: 0.01ms or 0.01µs depending on range & Cell factor TDS: 1ppm |
Auto Temp. Comp | 0-100˚C using PT100 external sensor |
Manual Temp. Comp | Settable from front panel from 0-100.0˚C |
Cond/TDS Calibration | Digital calibration by factor multiplication from 0.75-1.25 |
Recorder Output | Isolated 4-20mA => 0-2000 (for whatever unit and resolution selected (Maximum termination 250Ω) |
Control Output | Two set of NO-P-NC, 5 Amps potential free Relay Contacts Relay 1 ON, for Cond/TDS < Set Limit1 – Hysterises1, Relay 1 OFF, for Cond/TDS > Set Limit1 Relay 2 OFF, for Cond/TDS < Set Limit2,Relay 2 ON, for Cond/TDS > Set Limit2 + Hysterises2 |
Accuracy | 0.5% ± 1 Digit |
Supply | 220V AC ±10% @ 50Hz |
Enclosure | Plastic (ABS). Size -96x96x110mmm |
Low Voltage | Set at 10.5V internally. For testing 12V Battery AH |
Weight | 900 grams |