Thermocouple probes with colour-coded cables mounted on an industrial heat-treatment furnace

Thermocouple Colour Code Chart: Types J, K, T, E, N, R, S And B — ANSI vs IEC Colours, Ranges And Tolerances

In short: Identify a thermocouple by its negative lead: it is red in the ANSI (US) code and white in the IEC (Indian/European) code. The positive lead and jacket then tell you the type — e.g. IEC green = K, black = J, brown = T. Use K for most furnaces up to about 1200 °C, J for plastics and ovens up to about 750 °C, T for low temperatures, and R/S/B platinum types above about 1200 °C. Download our free colour and tolerance chart below.

Thermocouple colour code chart for types J, K, T, E, N, R, S and B showing ANSI and IEC colours

⬇ Download the free Countronics Thermocouple Chart (PDF, 2 pages)

Thermocouple Types at a Glance

TypeConductors (+ / −)Range (°C)IEC colour (+ / −)ANSI colour (+ / −)Typical use
JIron / Constantan−210 to 1200 (practical 0–750)Black / WhiteWhite / RedPlastics machinery, ovens
KChromel / Alumel−270 to 1372Green / WhiteYellow / RedFurnaces, kilns — most common type
TCopper / Constantan−270 to 400Brown / WhiteBlue / RedCold rooms, food, low temperature
EChromel / Constantan−270 to 1000Violet / WhitePurple / RedHighest output per °C, cryogenics
NNicrosil / Nisil−270 to 1300Pink / WhiteOrange / RedStable alternative to K at high temperature
RPt-13% Rh / Pt−50 to 1768Orange / WhiteBlack / Red (ext.)Glass, steel, high-temperature furnaces
SPt-10% Rh / Pt−50 to 1768Orange / WhiteBlack / Red (ext.)Lab reference, heat treatment
BPt-30% Rh / Pt-6% Rh0 to 1820Grey / WhiteGrey / RedVery high temperature, above 1000 °C

Ranges are the limits of the standard reference tables. The practical continuous limit depends on wire size, sheath material and atmosphere — a thin bare K wire will not last long at 1250 °C, while a heavy mineral-insulated K probe can.

How to Identify a Thermocouple by Its Colours

  1. Check the negative lead: red means the ANSI code; white means the IEC code (common in India and Europe).
  2. Look at the positive lead and jacket to find the type from the table above.
  3. Older equipment may follow other national codes (BS, DIN, JIS) — if colours do not match either table, measure the wire’s mV output against a known temperature or ask the supplier.

Which Thermocouple Type Should You Choose?

  • Up to about 750 °C, oxidation not severe: Type J — common on plastic extruders and moulding machines.
  • General purpose up to about 1200 °C: Type K — the default for furnaces, ovens and kilns.
  • Below 0 °C or where accuracy near room temperature matters: Type T, or consider a PT100 — see PT100 vs thermocouple.
  • Long-term stability at high temperature: Type N instead of K.
  • Above about 1200 °C: platinum types R or S; Type B above about 1400 °C.

For a deeper comparison, read types of thermocouples.

Thermocouple Tolerances (Limits of Error)

TypeASTM E230 standardASTM E230 specialIEC Class 1IEC Class 2
J±2.2 °C or ±0.75%±1.1 °C or ±0.4%±1.5 °C or ±0.4%±2.5 °C or ±0.75%
K / N±2.2 °C or ±0.75%±1.1 °C or ±0.4%±1.5 °C or ±0.4%±2.5 °C or ±0.75%
T±1.0 °C or ±0.75%±0.5 °C or ±0.4%±0.5 °C or ±0.4%±1.0 °C or ±0.75%
E±1.7 °C or ±0.5%±1.0 °C or ±0.4%±1.5 °C or ±0.4%±2.5 °C or ±0.75%
R / S±1.5 °C or ±0.25%±0.6 °C or ±0.1%±1.0 °C (to 1100 °C)±1.5 °C or ±0.25%

Above 0 °C, the larger of the two values applies; percentages are of the measured temperature in °C. Example: a standard-grade K thermocouple at 800 °C may be off by up to ±6 °C (0.75% of 800). Full temperature bands are in the PDF chart.

Extension and Compensating Cable

A thermocouple measures the temperature difference between its hot junction and the point where it connects to copper wiring. Extending it with ordinary copper cable moves that cold junction to the wrong place and adds errors. Always use extension or compensating cable of the same type and colour code, and keep polarity correct — a reversed pair reads lower or even negative as temperature rises.

Instruments for Thermocouples

Countronics temperature controllers, indicators and multi-channel data loggers accept J, K and R thermocouples (and PT100), with automatic cold-junction compensation. The CT716 logs up to 16 thermocouples straight to a USB pen drive.

Mistakes to Avoid

  1. Mixing ANSI and IEC colour cables on one installation.
  2. Extending a thermocouple with copper wire.
  3. Selecting the wrong type in the controller menu (K wire on a J setting reads tens of degrees off).
  4. Reversed polarity at the terminals.
  5. Using a thin bare-wire thermocouple near its maximum temperature for long periods.

Quick Checklist

  • Type matches process temperature
  • Colour code identified (ANSI or IEC)
  • Same-type extension cable
  • Polarity checked
  • Instrument set to the same type

Frequently Asked Questions

What colour is a K type thermocouple?

In the IEC code used in India and Europe, the K positive lead and sheath are green and the negative is white. In the ANSI (US) code, K is yellow positive and red negative.

How can I tell if a thermocouple is ANSI or IEC colour coded?

Look at the negative lead: red means ANSI, white means IEC.

What is the difference between J and K thermocouples?

J (iron/constantan) is used up to about 750 °C and suits plastics and ovens; K (chromel/alumel) covers up to about 1200 °C continuously and is the general-purpose furnace type.

What is the accuracy of a K type thermocouple?

Standard grade is ±2.2 °C or ±0.75% of reading, whichever is greater, above 0 °C; special limits are ±1.1 °C or ±0.4%.

Can I use copper wire to extend a thermocouple?

No. Use extension or compensating cable of the same thermocouple type, or the reading will be wrong.

Which thermocouple is best for high temperature?

For long-term use above about 1200 °C, platinum types R, S or B are used; Type N is a stable base-metal option up to about 1200 °C.

Need an Instrument for Your Thermocouples?

Countronics makes temperature controllers, indicators and data loggers for J, K and R thermocouples. Tell us your sensor and range.


In short: Identify a thermocouple by its negative lead: it is red in the ANSI (US) code and white in the IEC (Indian/European) code. The positive lead and jacket then tell you the
Thermocouple Colour Code Chart: Types J, K, T, E, N, R, S And B — ANSI vs IEC Colours, Ranges And Tolerances
In short: Measure conductivity of feed and permeate. Salt rejection % = (1 − permeate ÷ feed) × 100. A healthy RO often rejects around 95–99 %. A falling rejection or rising permeate
RO Plant Monitoring: Feed And Permeate Conductivity, Salt Rejection Calculation And Alarm Settings
In short: After a power cut, a timer either resets (starts again from zero), or resumes from where it stopped. Resume is essential for long processes such as curing and soaking; reset is
What Happens To A Timer When Power Fails? Reset, Resume And Battery Backup Explained