Ampere-hours are current multiplied by time. With a steady 50 A for 2 hours, the charge is 100 Ah. When the current varies, which it nearly always does, the meter adds up current × time continuously, so the total is still correct. If you are new to this, start with what an ampere-hour meter is and how it works.
Faraday’s law says the mass of metal deposited is proportional to the charge passed. For any metal, grams per Ah at 100% efficiency = atomic mass × 3,600 ÷ (valency × 96,485). Worked out for common plating metals:
| Metal (bath) | g per Ah at 100% | Density (g/cm³) | Typical cathode efficiency |
|---|---|---|---|
| Copper (acid, Cu²⁺) | 1.186 | 8.96 | 95–100% |
| Nickel (Watts, Ni²⁺) | 1.095 | 8.90 | 93–97% |
| Zinc (acid, Zn²⁺) | 1.220 | 7.13 | 90–98% (alkaline baths lower) |
| Tin (acid, Sn²⁺) | 2.214 | 7.29 | 90–100% |
| Silver (Ag⁺) | 4.025 | 10.49 | 95–100% |
| Gold (cyanide, Au⁺) | 7.349 | 19.32 | Varies widely with bath |
| Hard chrome (Cr⁶⁺) | 0.323 | 7.19 | 15–25% |
Efficiency figures are typical ranges; your bath supplier’s data sheet is the better source for your own process.
Say you need 10 µm of nickel on parts with a total area of 10 dm², at 95% efficiency.
Set the Ah meter preset to 8.6 Ah and the cycle will stop at the right coating weight even if the current wanders between 35 and 45 A. A timer set to 13 minutes would not.
Work out Ah per µm per dm² once for each bath. For the nickel above it is 8.6 ÷ (10 × 10) = 0.086. After that, preset = 0.086 × thickness × area. For example, 15 µm on 6 dm² needs 0.086 × 15 × 6 = 7.7 Ah.
The practical fix: calculate first, plate a trial batch, measure thickness at the thinnest critical point, then adjust the Ah preset. Once set, Ah control keeps it repeatable. For a precious-metal example, see why gold plating thickness varies batch to batch.
A battery’s rated capacity is the Ah it should deliver at a stated discharge rate, usually the 10-hour (C10) or 20-hour (C20) rate, down to a specified end voltage. To check it:
Example: the 150 Ah battery reaches cut-off after 8 h 20 min at 15 A. That is 125 Ah, or 83% of rated capacity. Batteries are commonly replaced once they fall below 80%.
For standby systems, see how to test UPS battery capacity.
To fully recharge a lead-acid battery you must put back more Ah than you took out, typically 10–20% more, because some current is lost to gassing and heat. Lithium-ion cells are far more efficient, close to 1:1. Meters with separate charge and discharge counters show both numbers, so you can see the actual ratio instead of guessing.
About 0.86 Ah, assuming 95% cathode efficiency. 10 µm of nickel on 1 dm² weighs 0.89 g, and 1 Ah deposits about 1.095 g of nickel at 100% efficiency.
Multiply by 3,600. One ampere-hour is one ampere flowing for 3,600 seconds, so 1 Ah = 3,600 C. To convert to ampere-minutes, multiply by 60.
The usual reasons are cathode efficiency below 100%, a larger real surface area than assumed (including racks, holes and the back side), and uneven current distribution, which makes edges thicker and recesses thinner. Calibrate the Ah setting against measured thickness on real parts.
Discharge the fully charged battery at its rated current to the specified cut-off voltage, read the ampere-hours delivered, and divide by the rated capacity. 125 Ah from a 150 Ah battery is 83%. Many maintenance practices replace a battery once it falls below 80%.
Yes, as long as the meter samples fast enough and integrates the actual current rather than estimating it from a peak or RMS value. The total charge is what matters, not the waveform.