Type K Thermocouple Guide: Range, Accuracy, Drift, Green-Rot And When To Choose Type N Instead

In short: Type K (Chromel/Alumel) is the general-purpose thermocouple: about −200 to +1250 °C, roughly 41 µV/°C, IEC colour green (+) / white (−). Standard accuracy is ±2.2 °C or ±0.75 % above 0 °C. It drifts with long use above about 1000 °C, can suffer “green-rot” in low-oxygen atmospheres around 800–1050 °C, and shows a small shift between about 250 and 550 °C. For long-term stability at high temperature, Type N is often better.

📘 Part of the Temperature Measurement Knowledge Hub — guides on thermocouples, PT100, controllers and data logging.

Key Data

PropertyType K
Positive legChromel (nickel-chromium)
Negative legAlumel (nickel-aluminium, slightly magnetic)
Table range−270 to 1372 °C
Practical continuous useUp to about 1100–1250 °C depending on wire size and sheath
SensitivityAbout 41 µV/°C
IEC 60584-3 coloursGreen (+), white (−), green sheath
ANSI coloursYellow (+), red (−)
Standard tolerance±2.2 °C or ±0.75 % (above 0 °C)
Special / Class 1±1.1 °C or ±0.4 %

Full colour and tolerance tables for all types are in our thermocouple colour code chart.

Why Type K Is So Popular

  • Wide range from cryogenic to furnace temperatures
  • Good oxidation resistance
  • Low cost compared with platinum types
  • Supported by virtually every controller, indicator and logger

Wire Size and Maximum Temperature

Thin wire responds fast but oxidises quickly. As a rough guide for bare Type K in clean air: heavy wire (around 3 mm) can be used near 1250 °C, while fine wire (around 0.3 mm) should stay well below about 870 °C. Mineral-insulated (MI) sheathed probes protect the wires and extend life; the sheath material (stainless steel, Inconel) sets its own limit.

Known Limitations

Drift at high temperature

Long use above about 1000 °C changes the alloy composition. The thermocouple slowly reads wrong — often several degrees over months. Replace thermocouples on a schedule in critical heat treatment.

Green-rot

In atmospheres with little oxygen (vacuum, reducing gases, inside long closed sheaths) between about 800 and 1050 °C, chromium in the positive leg oxidises preferentially. The leg turns green and the reading drops substantially. Use a sheath with enough internal air, a getter, or Type N.

Short-range ordering

Between about 250 and 550 °C the positive leg can change its internal structure, causing errors of a few degrees that partly reverse on heating above about 700 °C. For high-accuracy work in this band, consider Type N or a PT100.

K vs J vs N

Type JType KType N
Best range0 to about 750 °CUp to about 1250 °CUp to about 1250 °C
Stability at high temperatureIron leg oxidises above ~550 °C in airDrifts over timeBetter than K
SensitivityHigher (~52 µV/°C)~41 µV/°C~26 µV/°C
Typical usePlastics machineryFurnaces, generalLong-term high temperature

More comparisons: types of thermocouples.

Instruments for Type K

All Countronics thermocouple inputs accept Type K — see temperature controllers, the portable K thermocouple indicator and the CT716 16-channel logger.

Mistakes to Avoid

  1. Using fine-wire K near its upper limit for long periods.
  2. K in a sealed sheath in a reducing atmosphere (green-rot).
  3. Ignoring drift in critical furnace control.
  4. Mixing ANSI and IEC colour cables.

Quick Checklist

  • Wire size suits temperature
  • Sheath material suits atmosphere
  • Replacement schedule
  • Matching K extension cable
  • Instrument set to K

Frequently Asked Questions

What is the temperature range of a Type K thermocouple?

The standard table covers −270 to 1372 °C; practical continuous use is up to about 1100–1250 °C depending on wire size and sheath.

What colour is a Type K thermocouple in India?

Under the IEC code, the positive lead and sheath are green and the negative lead is white.

How accurate is a Type K thermocouple?

Standard grade is ±2.2 °C or ±0.75 % of reading above 0 °C, whichever is greater; special limits are ±1.1 °C or ±0.4 %.

What is green-rot in a K thermocouple?

Preferential oxidation of chromium in the positive leg in low-oxygen atmospheres at about 800–1050 °C, causing the reading to fall.

When should I use Type N instead of Type K?

For long-term use at high temperature where stability matters, or where green-rot is a risk.

Using Type K Thermocouples?

Countronics makes controllers, indicators and data loggers for Type K and other thermocouples. Tell us your process temperature.


In short: Most thermocouple faults are wiring, not the sensor. Check in this order: right type selected in the instrument → polarity at every joint → same-type extension cable (no copper) → connections
Thermocouple Troubleshooting: Wrong Readings, Reversed Wires, Noise, Drift And Open Circuits
In short: A thermowell is a closed tube welded or screwed into a pipe or vessel so the temperature sensor can be removed without draining or depressurising the process. It protects the sensor
Thermowell Guide: When You Need One, Insertion Length, Response Time And Materials
In short: A PT100 is a platinum resistor that measures 100 Ω at 0 °C and rises by about 0.385 Ω per °C (138.5 Ω at 100 °C). The instrument passes a small
How Does A PT100 (RTD) Work? Resistance vs Temperature, 2-, 3- And 4-Wire Connections And Class A vs B