| Property | Type K |
|---|---|
| Positive leg | Chromel (nickel-chromium) |
| Negative leg | Alumel (nickel-aluminium, slightly magnetic) |
| Table range | −270 to 1372 °C |
| Practical continuous use | Up to about 1100–1250 °C depending on wire size and sheath |
| Sensitivity | About 41 µV/°C |
| IEC 60584-3 colours | Green (+), white (−), green sheath |
| ANSI colours | Yellow (+), red (−) |
| Standard tolerance | ±2.2 °C or ±0.75 % (above 0 °C) |
| Special / Class 1 | ±1.1 °C or ±0.4 % |
Full colour and tolerance tables for all types are in our thermocouple colour code chart.
Thin wire responds fast but oxidises quickly. As a rough guide for bare Type K in clean air: heavy wire (around 3 mm) can be used near 1250 °C, while fine wire (around 0.3 mm) should stay well below about 870 °C. Mineral-insulated (MI) sheathed probes protect the wires and extend life; the sheath material (stainless steel, Inconel) sets its own limit.
Long use above about 1000 °C changes the alloy composition. The thermocouple slowly reads wrong — often several degrees over months. Replace thermocouples on a schedule in critical heat treatment.
In atmospheres with little oxygen (vacuum, reducing gases, inside long closed sheaths) between about 800 and 1050 °C, chromium in the positive leg oxidises preferentially. The leg turns green and the reading drops substantially. Use a sheath with enough internal air, a getter, or Type N.
Between about 250 and 550 °C the positive leg can change its internal structure, causing errors of a few degrees that partly reverse on heating above about 700 °C. For high-accuracy work in this band, consider Type N or a PT100.
| Type J | Type K | Type N | |
|---|---|---|---|
| Best range | 0 to about 750 °C | Up to about 1250 °C | Up to about 1250 °C |
| Stability at high temperature | Iron leg oxidises above ~550 °C in air | Drifts over time | Better than K |
| Sensitivity | Higher (~52 µV/°C) | ~41 µV/°C | ~26 µV/°C |
| Typical use | Plastics machinery | Furnaces, general | Long-term high temperature |
More comparisons: types of thermocouples.
All Countronics thermocouple inputs accept Type K — see temperature controllers, the portable K thermocouple indicator and the CT716 16-channel logger.
The standard table covers −270 to 1372 °C; practical continuous use is up to about 1100–1250 °C depending on wire size and sheath.
Under the IEC code, the positive lead and sheath are green and the negative lead is white.
Standard grade is ±2.2 °C or ±0.75 % of reading above 0 °C, whichever is greater; special limits are ±1.1 °C or ±0.4 %.
Preferential oxidation of chromium in the positive leg in low-oxygen atmospheres at about 800–1050 °C, causing the reading to fall.
For long-term use at high temperature where stability matters, or where green-rot is a risk.
Countronics makes controllers, indicators and data loggers for Type K and other thermocouples. Tell us your process temperature.