A “100 Ah” battery is rated to deliver its capacity over a stated time — for example the C10 rating means 10 A for 10 hours. Discharging faster gives less usable capacity, so tests must use the rate the manufacturer specifies.
| Chemistry | Nominal cell voltage | Typical charge limit | Typical discharge cut-off |
|---|---|---|---|
| Lead-acid (flooded / VRLA) | 2.0 V | about 2.35–2.45 V/cell (14.1–14.7 V for 12 V) | 1.75 V/cell (10.5 V for 12 V) |
| Lithium-ion (NMC) | 3.6–3.7 V | 4.2 V/cell | about 2.75–3.0 V/cell |
| LiFePO₄ | 3.2 V | 3.6–3.65 V/cell | about 2.5 V/cell |
| Ni-Cd | 1.2 V | constant-current, terminated by time or ΔV | 1.0 V/cell |
Always follow the battery maker’s datasheet for exact limits.
| Stage | What happens | Ends when |
|---|---|---|
| Constant current (bulk) | Charger holds a set current; voltage rises | Battery reaches the charge voltage limit |
| Constant voltage (absorption) | Voltage held; current tapers | Current falls to a small value (e.g. about C/20) |
| Float (lead-acid) | Lower voltage (about 2.25 V/cell) keeps the battery full | Continuous |
In battery factories, banks of rectifiers perform the formation charge on new batteries, where the Ah delivered to each circuit is a key quality parameter.
The test runs until the battery voltage reaches the cut-off. The capacity is the Ah delivered up to that point.
| Function | Why it matters |
|---|---|
| Integrates actual current over time | Gives true Ah even when a resistor load’s current drifts |
| Low-voltage cut-off | Ends the discharge exactly at the end voltage — the 810AH stops at 10.5 V for 12 V batteries — and avoids over-discharge |
| Preset Ah on charge | Stops charging after a set Ah input, e.g. for formation or equalising |
| Live current display | Operator sees the charge or discharge rate at a glance |
| Memory through power cuts | Long tests are not lost |
| Item | Value |
|---|---|
| Battery | 12 V, 100 Ah at C10 |
| Test | Discharge at about 10 A through a resistor bank to 10.5 V |
| Actual current | 10.2 A at start, 9.4 A near the end |
| Time to 10.5 V | 9 h 30 min |
| Ah meter reading | 92.0 Ah |
| Capacity | 92 % of rated |
Simply multiplying 10 A × 9.5 h would give 95 Ah — a 3 % error caused by the falling current. The Ah meter’s integrated reading is the correct one.
Batteries return less charge than they take. Lead-acid typically needs about 105–120 % of the discharged Ah to be fully recharged; lithium-ion is close to 99 %. Measuring Ah in on charge and Ah out on discharge with a meter on each circuit shows the efficiency and flags ageing cells. Background: what is an ampere-hour meter and ampere-hour calculations for battery testing.
The battery is discharged at its rated current to its cut-off voltage, and the ampere-hours delivered are measured. That figure is its actual capacity.
A transformer steps down AC, a diode or thyristor bridge converts it to DC, a filter smooths it, and a control loop regulates current and voltage.
Typically 10.5 V (1.75 V per cell) for capacity tests at the 10-hour rate.
Because the current changes during the test, especially with resistor loads. The Ah meter integrates the real current for an accurate capacity.
Constant-current charging until the voltage limit is reached, then constant-voltage charging while the current tapers off.
Yes. Models such as the Countronics 810AH stop at a low-voltage cut-off (10.5 V for 12 V batteries).
Countronics ampere-hour meters are used for battery formation, charge and discharge testing, with low-voltage cut-off and memory through power cuts. Tell us the battery voltage, capacity and test current.
By Countronics

By Countronics

By Countronics

© 2026 - countronics.com
WhatsApp us